• IEC Standard Toughened Glass Insulator
  • IEC Standard Toughened Glass Insulator
  • IEC Standard Toughened Glass Insulator
  • IEC Standard Toughened Glass Insulator

IEC Standard Toughened Glass Insulator

Application: High-voltage
Material: Toughened Glass
Structure: Suspension Insulator
Type: B Type Insulator
Usage: High Voltage Power Transmission
Connection Method: Plug in Socket Eye
Samples:
US$ 5/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Gold Member Since 2010

Suppliers with verified business licenses

Manufacturer/Factory, Other, Group Corporation

Basic Info.

Model NO.
U40B, U70B, U120B, U160B, etc
Size of Bearing Capacity
40KN
Certification
CE, ISO9001
Color
Cyan
Brand
Cowinelec, OEM or ODM
Mechanical Failing Load
40kn,70kn,120kn,etc
Raw Material
Toughened Glass
Transport Package
Wooden Case
Specification
Customizable
Trademark
COWINELEC, OEM or ODM
Origin
Zhejiang, China
HS Code
85461000
Production Capacity
30000PCS/Month

Product Description

Glass Insulator: U40B, U70 till to U550B; 40kN ---550kN;
Confirm with IEC60305
 
Type number Mechanical failing load(kN) Electromechanical load test value(KN /1hour) Unit spacing(mm) Nominal diameter(mm) Minimum nominal creepage distance(mm) 50%Lightning flashover voltage(peek)KV 1 minute wet withstand voltage(kv) Power Frequency puncture voltage(kv) unit weight(kg)
LXHY4-70 70 52.5 146 255 500 120 45 130 5.2
LXHY-100 100 75 146 255 500 120 45 130 5.2
LXHY-120 120 90 146 255 500 120 45 130 5.3
LXHY3-160 160 120 155 280 450 125 50 130 7.0
LXHY3-210 210 157.5 170 320 550 140 55 130 9.6
LXHY3-240 240 180 170 320 550 140 55 130 9.9
 

Glass insulator
Currency designation U160B/155 U210B/170 U240B/170
Designation LXP6-160 LXP6-210 LXP6-240
(mm)Diameter D 360 360 360
(mm)Spacing H 155 170 170
(mm)Creepage L 550 550 550
(mm)Socket soupling 20 20 24
(KN)Mechanical failing Load 160 210 240
(KN)Mechanical routine test 80 105 120
(KV)Wet Power frequency withstand voltage 45 45 45
(KV)Dry lighting impulse withstand voltage 110 110 110
(P.U)Impulse puncture voltage 2.8 2.8 2.8
(KV) Power frequency puncture voltage / / /
(μV)Rodio influence voltage(10KV, 1MHZ) 50 50 50
(KV)Corona visual test 18/22 18/22 18/22
power frequency electric arc voltage 0.12s/20kA 0.12s/20kA 0.12s/20kA
(kg)Net weight per unit 10.1 10.1 10.2

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Gold Member Since 2010

Suppliers with verified business licenses

Manufacturer/Factory, Other, Group Corporation
Management System Certification
ISO 9001, ISO 9000, ISO 14001, ISO 14000, ISO 14064
OEM/ODM Availability
Yes